Product Type : Fire Alarm
Product Category : Accessories Fire Alarm System
Product Model : SME-WMS2-CS
Product Status :
Non Discontinued
Operating voltage | DC (17 ~ 30) V |
Start-up time | ≤ 10 s |
Quiescent current | 650 µA |
Alarm current | 1.5 mA |
Fault current | 1.2 mA |
Number of outputs a | 1 |
Output current | 800 mA |
Output type | Solid state FET |
External switched supply | DC (17 ~ 30) V |
Bi-stable output period b | 700 ms (350 ms On / 350 ms Off) |
Alarm indicator | Red |
Polling indicator | Flashing green |
Fault indicator | Yellow |
Terminal wiring | (0.4 ~ 2.5) mm2 |
End-of-line device | 10 kΩ |
Usable addresses per alarm loop | 32 |
Operating temperature | (-10 ~ +55) °C |
Operating humidity | (0 ~ 95) % RH, non-condensing |
Storage temperature | -25 ~ +80) °C |
Storage humidity | (0 ~ 98) % RH, non-condensing |
Dimensions (h × w × d) | (95 × 95 × 42) mm |
Ingress protection rating | IP-54 |