Product Type : Fire Alarm
Product Category : Accessories Fire Alarm System
Product Model : SME-WMS2-IM
Product Status :
Non Discontinued
Operating voltage | DC (17 ~ 30) V |
Start-up current | ≤ 1.5 mA |
Start-up time | ≤ 10 s |
Input voltage (pulsed) | DC (5 ~ 9) V |
Quiescent condition input resistance | (8k2 ~ 47k) Ω |
Quiescent current with 22 kΩ EOL fitted | ≤ 700 µA |
Sampling time | 1 s |
Polling indicator | Flashing green |
Alarm condition input resistance | (2k2 ~ 8k2) Ω |
Alarm current | 2 mA |
Alarm indicator | Red |
Input short-circuit Fault condition resistance | ≤ 2k2 Ω |
Input open-circuit Fault condition resistance | ≥ 47 kΩ |
Switching current (max) | 1.0 A |
Switching resistance (max) | 0.3 Ω |
Isolator indicator | Yellow |
Operating temperature | (-10 ~ +50)°C |
Operating humidity | (0 ~ 95) % RH, non-condensing |
Storage temperature | (-25 ~ +80)°C |
Storage humidity | (0 ~ 98) % RH, non-condensing |
Number of inputs | 1 |
Usable addresses per alarm loop | 125 |
Terminal wiring | (0.4 ~ 2.5) mm2 |
Dimensions (h × w × d) | (95 × 95 × 42) mm |
Ingress protection ratin | IP-54 |