Call us now +44-2086050815







Product Details


Details



Conventional Natural Gas Alarm

Product Type : Fire Alarm
Product Category : Conventional Control Fire Alarm System
Product Model : SOHO-WN2-EN
Product Status : Non Discontinued


Downloads



Product Features

  • Advanced algorithms provide advanced detection discrimination.
  • Stable gas sensing chamber. No adjustment or replacement required.
  • High immunity against unwanted alarms.
  • Surface-mount device (SMD) circuit board design.
  • DC 12 V or DC 24 V operation.
  • Loud 85 dB internal sounder.
  • Audible warning signal of an internal fault.
  • N/C or N/O alarm relay output option.
  • Remote LED output option.
  • Easy installation. No programming required.
  • Connectable to zone monitor for use with addressable control and indicating equipment.
  • Sleek, low-profile housing design.
  • Low maintenance.

Product Specifications

Power

Operating voltage DC (10.8 ~ 33) V ,DC (10.8 ~ 26.4) V
Start-up current ≤ 100 μA , 120 mA
Start-up time ≤ 10 min
Quiescent current 50 μA , 60 mA
Quiescent condition indicator Green LED flashing every 5 s

 

Alarm Condition

Sampling time (2 ~ 4) s
Alarm response threshold (0.10 ±0.04) LEL CH4 (natural gas)
Alarm condition indicator Red LED
Sounder output ≥ 85 dB / 3 m
Alarm current (max) 50 mA / DC 24 V
Alarm relay SPST. N/O or N/C. 1.0 A
/ DC 30 V /
0.5 A / AC 125 V
Remote LED output current (max) 15 mA

 

Fault Condition

Internal fault indication Single short audible signal every 30 s

 

Reset

Reset voltage ≤ 1 V
Reset time ≤ 5 s

 

Environmental

Operating temperature (-10 ~ +50)°C
Operating humidity (0 ~ 95)% RH, non-condensing
Storage temperature (-25 ~ +80)°C
Storage humidity (0 ~ 98)% RH, non-condensing

 

Miscellaneous

Dimensions Φ 102 mm × 45 mm
Ingress protection rating IP-42