Call us now +44-2086050815







Product Details


Details



Conventional Control Panel

Product Type : Fire Alarm
Product Category : Conventional Control Fire Alarm System
Product Model : SOHO-WMP2-EN ,SOHO-WMP4-EN ,SOHO-WMP8-EN
Product Status : Non Discontinued


Downloads



Product Features

  • 2, 4, or 8 detection zones.
  • Supports up to 32 conventional devices per alarm zone circuit.
  • Configurable non-latching alarm zones1.
  • Configurable timer to delay output activation (up to 10 min).
  • Capacitor end-of-line device.
  • 3 Access Levels.
  • Single-person test mode.
  • Day/night mode configurable.
  • Manual activation of alarm devices.
  • Auxiliary DC 24 V output, with short-circuit protection.
  • Optional detection zone N/O and N/C relay outputs.
  • Clear alarm zone LED indicators, with a single indicator for Fault, Disable, and Test Condition indication.
  • Supports up to 7 Repeater Panels.
  • Easy installation.

Product Specifications

Power Supply

MODEL  SOHO-WMP2-EN SOHO-WMP4-EN SOHO-WMP8-EN
Operating Voltage AC (85 ~ 260) V / 50/60 Hz
Mains supply current limit  720 mA / AC 230 V
Mains supply fuse 4 A / AC 250 V slow blow (20 mm)
Mains supply fault threshold voltage ≤ AC 60 V
Power supply 2.2 A / DC 28.5 V
Quiescent current 45 mA
Maximum continuous output current (Ia, max) 0.425 A
Maximum continuous output current
(Ib, max)
1.3 A
Standby battery maximum capacity (2
× DC 12 V)
7.2 Ah
Maximum battery current draw 1.5 A / maximum operating temperature
Battery fuse 6 A resettable (electronic fuse)
Battery fault threshold voltage < DC 20 V
Battery fault threshold internal resistance 0.5 Ω

 

Detection Zones

Detection zone circuits  2 ,4 , 8
Number of connected devices per 32
Detector zone quiescent current 5 mA
Detector zone alarm current 40 mA  , 80 mA  ,160 mA
Detector zone wiring characteristics
(max)
40 Ω / 0.47 μF
Detection zone end-of-line capacitor 10 μF / DC 50 V
Manual call point resistor value (470 ~ 689) Ω

 

Alarm Zones

Alarm zone outputs 2
Alarm zone current 700 mA
Alarm zone end-of-line resistor 100 kΩ
Alarm zone monitoring Open- and short-circuit
Alarm zone voltage (max) DC 27.5 V
Alarm zone fuse 1.1 A resettable (electronic fuse)

 

Ancillary Outputs

Number of programmable output relays 2
Ancillary fire C/O relay 2 × (1.0 A @ DC 30 V / 1 A @ AC 240 V)
Ancillary fault N/C relay 1.0 A @ DC 30 V / 1 A @ AC 240 V
Auxiliary supply DC (12.0 ~ 28.2) V @ 200 mA
Auxiliary supply at Ib, min DC (19.5 ~ 29.0) V @ 0 mA


Ancillary Inputs

Evacuation Start / Stop Non-latching, voltage-free
Day / Night Mode Non-latching, voltage-free
Remote Reset Non-latching, voltage-free


Miscellaneous

Terminal Wiring (0.4 ~ 2.5) mm2
Operating Temperature (0 ~ +50) °C
Operating Humidity (0 ~ 95) % RH, non-condensing
Storage Temperature (-25 ~ +80) °C
Storage Humidity (0 ~ 98) % RH, non-condensing
Dimensions (H × W × D) (402 × 337 × 99) mm
Weight (Excluding Batteries) 4.0 kg